3200A Draw out Vacuum Intelligent Circuit Breaker

3200A Draw out vacuum intelligent  circuit breaker Universal Air circuit breaker is designed to distribute and protect circuit and equipment fromoverload, under-voltage short-circuit damage ,and single-phase earthing .Rated current: 1600a,2000a,2500a,3200a,4000a,6300aNo of poles: 3P,4PRated insulation vo

Featured Products

3200A Draw out vacuum intelligent  circuit breaker 
Universal Air circuit breaker is designed to distribute and protect circuit and equipment from
overload, under-voltage short-circuit damage ,and single-phase earthing .
Rated current: 1600a,2000a,2500a,3200a,4000a,6300a
No of poles: 3P,4P
Rated insulation voltage: 400v/690v
 Icu(kA)O-CO : 100kA/400v, 65kA/690v
  Ics(kA)O-CO-CO: 65kA/400v, 50kA/690v
  Icw(kA)O-CO: 65kA/400v, 50kA/690v
  Standard : IEC60947-2. 
  Arcing over distance: 0mm
  Inherent making & breaking time:  23-32ms
  Mechanical life : 10000 times

3200A Draw out type 4pole intelligent  air circuit breaker     

Type

                             
DW45-1600                             

DW45-2000
DW45-3200DW45-4000DW45-6300

Frame rated
current Inm (A)

1600
2000320040006300
Number of poles3,43,43,43,43,4
Rated current In (A)
200,400,630,
800,1000

400,630,800,1000,
1250,1600,2000

2000,2500,2900,3200

2000,2500,3200,4000
4000,5000,6300
Icu (kA)O-CO400V4280100100120
690V2550656580
Ics (kA)O-CO-CO400V3050656580
690V2040505070
Icw(kA)O-CO400V20506565/80(MCR)85/100(MCR)
690V20405050/65(MCR)65/75(MCR)

Current at N-pole In (A)

50%In, 100%In

 
 

Inherent breaking time

23-32ms

 
 

Operational performance (operations)

Electric

500
Mechanical lifeMaintenance-free 2500    Maintenance 10000

Mounting Mode

Fixed with drawable

Arcing distance(mm)

0