CNC Acb Ycw1 2000A Air Circuit Breaker

CNC ACB YCW1 2000A Air Circuit BreakerYCW1 series intelligent air circuit breaker (hereinafter called ACB) are applied to the network circuit of AC 50 Hz, rated voltage 400V, 690V and rated current between 400A and 6300 A. Mainly used foe distributing energy and protecting the circuit and power supply device against short-circui

Featured Products

CNC ACB YCW1 2000A Air Circuit Breaker

YCW1 series intelligent air circuit breaker (hereinafter called ACB) are applied to the network circuit of AC 50 Hz, rated voltage 400V, 690V and rated current between 400A and 6300 A. Mainly used foe distributing energy and protecting the circuit and power supply device against short-circuit, under-voltage, single-phase ground fault, etc. The ACBS has intelligent protection function and the key parts adopt intelligent release. The release can make the accurate selective protection, which can avoid cutting off the power and improve the reliability of power supply.
The products conform to IEC60947-2, IEC 60947-4 standards

YCW1 Air Circuit Breaker
1. Standard: IEC60947-1, IEC60947-2
2. Rated current: 630~6300A
3. AC 50Hz rated voltage 400V, 690V
4. Fixed & withdraw type
5. Output: 2000PCS/day
6. CE, CB, ISO9001, 14001, IEC
7. OEM

Key Words: Intelligent Universal Circuit Breaker, Breaker, Circuit Breakers, Acb, Low Voltage Circuit Breaker, Circuit Breaker Panel, Air Circuit Breaker, Circuit Breaker Trip, Breaker Protector, Vacuum Circuit Breaker
TypeYCW1-2000YCW1-3200YCW1-6300
Pole3P, 4P3P, 4P3P, 4P
Using categaryBBB
Rated current InA630, 800, 1000, 1250, 1600, 20002000, 2500, 30004000, 5000, 6300
Rated frequencyHz505050
Rated operation voltage UeV400, 690400, 690400, 690
Rated insulation voltage UiV800800800
Arcing distancemm000
Rated impulse withstanding voltage Uimp V800080008000
Rated operation short circuit breaking capacity Ics(O-t-CO-t-CO)400Vka5080100
690Vka405075
Rated limiting short circuit breaking capacity Icu(O-t-CO)400Vka80100120
690Vka506585
Rated short circuit closing capacity Icm400Vka176220264
690Vka105143187
Rated short time withstanding current Icw(O-t-CO, AC400V 0.4s)400Vka506585
Operation lifeper hourTimes202010
ElectricalTimes1000500500
MechanicalTimes1000050005000
Full breaking timems20~3020~3020~30
Full closing timems55~7055~7055~70
Power consumption3PW36012002000
4PW45017502300
Resistance of each poleFixed typeμ Ω119-
Draw out typeμ Ω201410
Dimensions(L*W*H)3P fixed typemm362*323*402422*323*402 
3P draw out typemm375*461*452435*471*452 
4P fixed typemm457*323*402537*323*402 
4P draw out typemm470*461*452550*471*452 
Approximate weight 3P fixed typekg4155 
3P draw out typekg7195245
4P fixed typekg51.565 
4P draw out typekg86115260


CNC Acb Ycw1 2000A Air Circuit Breaker
 