Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker

DC1000V 4 Pole 6A-63A DC Circuit Breaker DC MCB for Solar Switch TUV SAA CE CertificateDC1200V 63A DC Circuit breaker for solar switch has passed IEC, TUV, CE certificateDC circuit breaker\'s ApplicationGL7-63 Series DC1200V 63A DC Circuit breaker, apply to rating current 63A or less, It is mainly used for the overloading and sh

Featured Products

Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker

Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker
Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker
Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker
Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker
DC1000V 4 Pole 6A-63A DC Circuit Breaker DC MCB for Solar Switch TUV SAA CE Certificate

DC1200V 63A DC Circuit breaker for solar switch has passed IEC, TUV, CE certificate
DC circuit breaker's Application
GL7-63 Series DC1200V 63A DC Circuit breaker, apply to rating current 63A or less, It is mainly used for the overloading and short circuit protection in DC distribution system equipment and electric equipment. It can be widely used in electric, post, traffic, mining enterprise and different kinds of fields. In present China, our products in the case grade rating voltage is highest compared to the same products.
Standard
Products according IEC60947, GB14048.2, IEC60898.2 AS/NZS60898.1, AS/NZS60898.2, AS/NZ61009
Standard.
Technical DataIEC 898
Standards1P/2P/3P / 4P
PolesC
Magnetic tripping characteristics6 10 16 20 25 32,40,50,63A
Rated current(A)6kA
Rated short-circuit capacity(Icn):DC250V DC550V DC750V DC800V DC1000V DC1200V
Rated voltage6kV
Rated withstand voltage (Uimp):1000
Rated insulation voltage(Ui):Yes
Contact position indication3
Energy limiting class:>2000
Electrical Life:>1500
Mechanical Life:Screw terminal
Connection terminal:Pillar terminal with clamp

 
1~16mm
Connection capacity:Symmetrical DIN rail 35mm
Installation:Panel mounting

 
OF: Auxiliary contact
Accessories:FB: Auxiliary alarm

 
QY: under/over volage protector

 
FL: Shunt release
Overload Characteristic
TestTypeCurrentStart StateTrip / Not-trip
Time Limit
Expected
Result
Note
ac1.05 lnColdt ≥1hNot-trip
 
bc1.30 lnFoollows test at<1hTripThe current will rise to expected value within 5S
cc7 lnColdt ≥0.1sNot-trip
 
dc15lnColdt<0.1sTrip
 

Electrical DC Circuit Breaker/Automatic Circuit Breaker/Miniature Circuit Breaker

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours